The following are copies of Code sections that apply to your
questions.
225-31. Disconnecting Means
Means shall be provided for disconnecting all ungrounded
conductors that supply or pass through the building or structure.
225-32. Location
The disconnecting means shall be installed either inside or
outside of the building or structure served or where the
conductors pass through the building or structure. The
disconnecting means shall be at a readily accessible location
nearest the point of entrance of the conductors. For the purposes
of this section, the requirements in Section 230-6 shall be
permitted to be utilized.
Exception No. 1: For installations under single management, where
documented safe switching procedures are established and
maintained for disconnection, the disconnecting means shall be
permitted to be located elsewhere on the premises.
225-33. Maximum Number of Disconnects
(a) General. The disconnecting means for each supply permitted by
Section 225-30 shall consist of not more than six switches or six
circuit breakers mounted in a single enclosure, in a group of
separate enclosures, or in or on a switchboard. There shall be no
more than six disconnects per supply grouped in any one location.
250-32. Two or More Buildings or Structures Supplied from a
Common Service
(a) Grounding Electrode. Where two or more buildings or
structures are supplied from a common ac service by a feeder(s)
or branch circuit(s), the grounding electrode(s) required in Part
C of this article at each building or structure shall be
connected in the manner specified in (b) or (c). Where there are
no existing grounding electrodes, the grounding electrode(s)
required in Part C of this article shall be installed.
Exception: A grounding electrode at separate buildings or
structures shall not be required where only one branch circuit
supplies the building or structure and the branch circuit
includes an equipment grounding conductor for grounding the
noncurrent-carrying parts of all equipment.
(b) Grounded Systems. For a grounded system at the separate
building or structure, the connection to the grounding electrode
and grounding or bonding of equipment, structures, or frames
required to be grounded or bonded shall comply with either (1) or
(2).
(1) Equipment Grounding Conductor. An equipment grounding
conductor as described in Section 250-118 shall be run with the
supply conductors and connected to the building or structure
disconnecting means and to the grounding electrode(s). The
equipment grounding conductor shall be used for grounding or
bonding of equipment, structures, or frames required to be
grounded or bonded. Any installed grounded conductor shall not be
connected to the equipment grounding conductor or to the
grounding electrode(s).
(2) Grounded Conductor. Where (1) an equipment grounding
conductor is not run with the supply to the building or
structure, and (2) there are no continuous metallic paths bonded
to the grounding system in both buildings or structures involved,
and (3) ground-fault protection of equipment has not been
installed on the common ac service, the grounded circuit
conductor run with the supply to the building or structure shall
be connected to the building or structure disconnecting means and
to the grounding electrode(s) and shall be used for grounding or
bonding of equipment, structures, or frames required to be
grounded or bonded.
(c) Ungrounded Systems. The grounding electrode(s) shall be
connected to the building or structure disconnecting means.
(d) Disconnecting Means Located in Separate Building or Structure
on the Same Premises. Where one or more disconnecting means
supply one or more additional buildings or structures under
single management, and where these disconnecting means are
located remote from those buildings or structures in accordance
with the provisions of Section 225-32, Exception Nos. 1 and 2,
all of the following conditions shall be met.
1. The connection of the grounded circuit conductor to the
grounding electrode at a separate building or structure shall not
be made.
2. An equipment grounding conductor for grounding any noncurrent-
carrying equipment, interior metal piping systems, and building
or structural metal frames is run with the circuit conductors to
a separate building or structure and bonded to existing grounding
electrode(s) required in Part C of this article, or, where there
are no existing electrodes, the grounding electrode(s) required
in Part C of this article shall be installed where a separate
building or structure is supplied by more than one branch circuit.
3. Bonding the equipment grounding conductor to the grounding
electrode at a separate building or structure shall be made in a
junction box, panelboard, or similar enclosure located
immediately inside or outside the separate building or structure.
(e) Agricultural Buildings or Structures. Where livestock is
housed, any portion of the equipment grounding conductor run
underground to the building or structure disconnecting means
shall be insulated or covered copper.
FPN: See Section 547-8 for special grounding requirements for
agricultural buildings.
(f) Grounding Conductor. The size of the grounding conductor to
the grounding electrode(s) shall not be less than given in Table
250-122, and shall not be required to be larger than the largest
ungrounded supply conductor. The installation shall comply with
Part C of this article.
Have fun with your interpretation
Wg
re: Detached Garage sub-panel |
Reuben |
4:07 pm sunday september 9, 2001 |
Thanks for the response.
I have indeed installed a separate ground rod for the garage
panel. Lets say my panel has only 6 circuits. Should I bond the
neutral bar to the ground bar? I'm not as interested in
interpreting the code as I am in having a safe electrical system.
Thanks again.
re: Detached Garage sub-panel |
Warren Goodrich |
5:57 pm sunday september 9, 2001 |
Yes you must marry any main panel in a detached garage that has a
common service fed from the main structure as long as you did not
run a fourth equipement grounding conductor with the feeder. If
your ran a fourth wire then you would have to separate the
neutral and grounding bars in that panel located in that detached
structure.
You said you did not run an equipment grounding conductor with
the feeder, therefore you must marry the neutral bar and the
grounding bar as one entity in that detached garage panel.
I understand you don't want to worry about interpretation as to
the NEC code requirements. However you must interpret it or have
it interpreted for you. If you do not meet the Code requirements
of the NEC then you did not meet the minimum safety standards set
forth by the largest part of the world. The NEC is considered in
most parts as a rule of law setting the minimum safety standards.
If you do not meet those NEC rules and something happens such as
structural damage or bodily injury, you will be held financially
liable. As I understand your discription of your wiring method
then you have met the NEC as long as you have no more than 6
circuits available in that garage panel and if you married the
neutral and grounding bar as one entity.
Good Luck
Wg
re: Detached Garage sub-panel |
Reuben |
6:53 pm sunday september 9, 2001 |
Thank you.
If sometime in the future I would need more than 6 circuits would
I meet code by using a panel that had it's own main disconnect?
Thanks.
re: Detached Garage sub-panel |
Reuben |
8:06 pm sunday september 9, 2001 |
If I use OSHA Lockout-Tagout procedures I interpret my garage as
being Exception No. 1 of 225-23.
What do think?
Thanks.
re: Detached Garage sub-panel |
wirenuts |
8:57 pm sunday september 9, 2001 |
It's nice that you are aware of LOTO, but i do not have a 225-23
in my 99' nec, is this a typo???
re: Detached Garage sub-panel |
Reuben |
9:00 pm sunday september 9, 2001 |
Sorry......225-32. Location....
Thanks for the response.
re: Detached Garage sub-panel |
wirenuts |
9:01 pm sunday september 9, 2001 |
Rueben;
by code, with a 3-wire, the G & N are married and bonded to the
panel, there is a GEC (grounding electrode conductor) from this
to an entirely new grounding electode system , that would equal
the home serving it. Note there can be no mutual mettalic paths
bettween house and garage here, the fear being a parralleled
nuetral.
re: Detached Garage sub-panel |
Warren Goodrich |
8:50 am monday september 10, 2001 |
Actually you should check out not only 225-32 but also 250-32-d.
I know this will cause some more confusion but special grounding
considerations have to apply using a common service concerning
that grounding of those two buildings.
Wirenuts, how do you read 250-32.
As for a lock out tag out, this term is only mentioned for
disconnects of motor loads. I am not sure which way [whether lock
out tag out would be required by your AHJ] considering accessory
buildings located on the same premises.
Curious
Wg
re: Detached Garage sub-panel |
Reuben |
12:17 pm monday september 10, 2001 |
After several hours of ruminating my interpretations are:
225-32 Location Exception #1: I can use my garage panel as a
subpanel in a remote location on the same premises under single
management.
250-32(d)1: I should not bond the neutral bar with the garage
grounding electrode.
250-32(d)3: The garage panel needs to have it's own grounding
electrode connected to the equipment ground bar.
Does this sound reasonable?
Thanks for everyone's help!
re: Detached Garage sub-panel |
Warren Goodrich |
6:11 pm monday september 10, 2001 |
You skipped the main road block in doing what you want to do.
REMEMBER THAT GROUNDED MEANS NEUTRAL CONDUCTOR AND GROUNDING
MEANS EQUIPMENT GROUNDING CONDUCTOR.
250-32-D requires that three requirments must be met before you
can use 225-32 speaking of that remote disconnect.
250-32-D-2 specifically says that you must run an equipment
grounding conductor with the feeder from the main building.
250-32-D specifically says that you must meet all three
requirements which would include requirment #2 demanding an
equipment grounding conductor be ran with the feeder between the
two buildings.
You only ran two hots and a neutral but no 4th conductor being
the equipment grounding conductor.
Therefore you must marry the neutrals and grounding bars together
as one entity and supply a main breaker serving as the main
disconnect form and overcurrent device as dictated in 225-32 and
250-32-B-2
See below the copies of the codes dictating that you locate the
main disconnect at that second building due to no equipment
grounding conductor ran with the feeder from that main building.
Also see below the copies of the codes dictating that the neutral
and grounding bar must be married.
225-32. Location
The disconnecting means shall be installed either inside or
outside of the building or structure served or where the
conductors pass through the building or structure. The
disconnecting means shall be at a readily accessible location
nearest the point of entrance of the conductors. For the purposes
of this section, the requirements in Section 230-6 shall be
permitted to be utilized.
250-32. Two or More Buildings or Structures Supplied from a
Common Service
(d) Disconnecting Means Located in Separate Building or Structure
on the Same Premises. Where one or more disconnecting means
supply one or more additional buildings or structures under
single management, and where these disconnecting means are
located remote from those buildings or structures in accordance
with the provisions of Section 225-32, Exception Nos. 1 and 2,
all of the following conditions shall be met.
2. An equipment grounding conductor for grounding any noncurrent-
carrying equipment, interior metal piping systems, and building
or structural metal frames is run with the circuit conductors to
a separate building or structure and bonded to existing grounding
electrode(s) required in Part C of this article, or, where there
are no existing electrodes, the grounding electrode(s) required
in Part C of this article shall be installed where a separate
building or structure is supplied by more than one branch circuit.
COMMENT;
The above requires that the main disconnect must be located at
the second building because of the lack of the 4th equipment
grounding conductor ran with the feeder from that main building.
Exception 1 in 225-32 can not be used because all three
conditions were not met in 250-32-D.
SEE A CONTINUATION OF THIS REPLY ON THE NEXT REPLY SHOWN, DUE TO
THE LENGTH OF THIS REPLY AND THE LIMITS OF THIS FORUM, IT HAS
BEEN SPLIT INTO TWO SECTIONS.
Wg
re: Detached Garage sub-panel |
Warren Goodrich |
6:16 pm monday september 10, 2001 |
250-32. Two or More Buildings or Structures Supplied from a
Common Service
(b) Grounded Systems. For a grounded system at the separate
building or structure, the connection to the grounding electrode
and grounding or bonding of equipment, structures, or frames
required to be grounded or bonded shall comply with either (1) or
(2).
(2) Grounded Conductor. Where (1) an equipment grounding
conductor is not run with the supply to the building or
structure, and (2) there are no continuous metallic paths bonded
to the grounding system in both buildings or structures involved,
and (3) ground-fault protection of equipment has not been
installed on the common ac service, the grounded circuit
conductor run with the supply to the building or structure shall
be connected to the building or structure disconnecting means and
to the grounding electrode(s) and shall be used for grounding or
bonding of equipment, structures, or frames required to be
grounded or bonded.
COMMENT;
You ran as a feeder from the main building to the second
building; two hots and a neutral with no equipment grounding
conductor ran with that feeder. Therefore the above rule applies
requiring that the neutral and grounding bar be joined as one
entity in that second buildings panel as required in 250-32-B-2.
CLOSING COMMENT;
Now you still can get by without a main disconnect if your panel
only has a maximum number of breaker openings of 6 circuits. If
that panel is capable of accepting more than 6 circuits then you
must install the main disconnect and main overcurrent device
usually being one main breaker in that panel using a main service
rated panel.
The following is a copy of that 6 main disconnect rule.
225-33. Maximum Number of Disconnects
(a) General. The disconnecting means for each supply permitted by
Section 225-30 shall consist of not more than six switches or six
circuit breakers mounted in a single enclosure, in a group of
separate enclosures, or in or on a switchboard. There shall be no
more than six disconnects per supply grouped in any one location.
Exception: For the purpose of this section, disconnecting means
used solely for the control circuit of the ground-fault
protection system, installed as part of the listed equipment,
shall not be considered a supply disconnecting means.
(b) Single-Pole Units. Two or three single-pole switches or
breakers, capable of individual operation, shall be permitted on
multiwire circuits, one pole for each ungrounded conductor, as
one multipole disconnect, provided they are equipped with handle
ties or a master handle to disconnect all ungrounded conductors
with no more than six operations of the hand.
May not be what you wanted to hear but thats the code sections
involved in your design with no equipment grounding conductor ran
with the feeder to that second building.
Hope this helps
Wg
re: Detached Garage sub-panel |
Reuben |
8:13 pm monday september 10, 2001 |
Thanks for all your help.My panel has room for 8 circuits. I
guess I need to purchase a 100A breaker for it to use as a main
disconnect. I assume I hook the 2 hot wires directly to the
breaker and leave the neutral where it is on the neutral bar. I
need to bond the neutral bar to the equipment ground bar. Does
this sound like it meets code?
As an alternative could I interupt the supply lines with an
equipment disconnect switch and use it for the main disconnect
freeing up all 8 circuits in my sub-panel?
Thanks.
re: Detached Garage sub-panel |
Warren Goodrich |
10:47 pm monday september 10, 2001 |
Depending on you panel will tell you how to join the neutral bar
and grounding bar. If you have a grounding bar that is bolted
directly to the case of the panel, and if this panel is also a
main service rated panel, then you should have a bonding jumper
with a green screw that is designed to attach to the neutral bar
and then bolt to the case of the panel. This will join the two
bars. Another method of bonding these two bars together again
depending on the brand of panel is a long green screw that passes
through the neutral bar and screws to the case of the panel.
Now to get a bit technical, when a main breaker is installed in a
panel that main breaker is supposed to be securely mounted to the
panel buss. Ususally a bracket clips that main breaker into place.
If you have a not service rated panel then you may not have a
means to bond the neutral bar properly or clip in the main
breaker.
A way to solve having a nonservice rated panel delemma is what
you mentioned. Add a 100 amp breaker style disconnect ahead of
that panel and make that panel a sub panel.
If you do this then you must marry the neutral and grounding bars
in that main breaker style disconnect. Then you must separate the
neutral and ground bar in that sub panel now being fed through
that main breaker disconnect.
Here we go again, confusing, ain't it ?
Wg
re: Detached Garage sub-panel |
Reuben |
7:26 am tuesday september 11, 2001 |
Thanks for all your help!
My panel is service rated. It tells me to buy retaining kit
#PK2MB for a breaker used as a main.
This forum has been a Godsend for me.
Thanks again!
re: Detached Garage sub-panel |
Warren Goodrich |
6:08 pm tuesday september 11, 2001 |
Glad to be of help to you. We hope you good luck with the rest of
your project.
Wg
This is 1 item from the Home Wiring
Forum Archives, to go to the main page of the forum archives then click HERE.
To go to the main page of the Home
Wiring Site , click HERE.