Pool Wiring / GFCI |
---|
Jeff Weik | 10:32 pm sunday september 9, 2001 |
---|
I'm having an inground pool installed (steel wall, vinyl liner).
I'm tackling the electrical rough-in work myself (running
conduit and pulling wires). The final connections will be made
by the installer's electrician.
My question regards the use of GFCI protection on the circuits
for the pool pump and for the pool light.
The installer said I do NOT need GFCI protection for the pump.
The pump will be hardwired on a dedicated circuit from the
panel. A timer box will be mounted near the pump and also serve
as the disconnect. The pump is 1.0HP, factory-set for
230V/10A. The installer told me that I should install a double
pole 20A breaker for the pump. Is this correct that I don't
need a GFCI breaker? And do I need a 20A breaker, when the pump
literature specifies only 10A?
For the pool light, the installer said I do need GFCI protection.
My question here is whether or not I need the light on a
dedicated circuit? Since the light is just 300W, I would like
to add more load to this circuit...such as landscape lighting
(probably another 200W), and possibly 1 or 2 outlets. I was
thinking that I could wire a 15A circuit to provide a GFCI
outlet near the pump pad, continue on to a low voltage
transformer/timer for landscape lighting, a switched branch for
the pool light, and a branch for 1-2 outlets by the pool patio
area. Would this be allowed by the NEC?
Hi Jeff,
your electrician is correct as to NEC on a hardwired pool, but
know that just because this level of protection is not required,
does not mean you are in any violation should you choose to
supply it.
it also sounds like you have a 'wet nitch' pool fixture here,
which does need GFI protection. The circuit you have described to
do this, as well as the GFI required within the pool area and the
landscape low-v is debatable concerning the configuration of
stringent grounding/bonding required of wet nitch fixtures. As
this gets to be sort of a lengthly explanation i think it best to
wait for Warren to reply
Yes, it is a wet niche light.
As I remember it you must run a dedicated branch circuit for the
pool pump then another for the pool light whether low voltage or
not. insulated 12 ga equipment grounding conductor must be
installed with each branch circuit and connected directly to the
main panel. An exception allows you to land them at a pool sub
panel as long as that pool sub panel is feed by a 4 wire cable
with the grounding conductor feeding that pool panel also
insulated. Check the section wiring a pool on this site. I will
get back around lunch to provide the Code numbers and confirm
what I am remembering.
See ya then
Wg
Warren,
Are you saying that the underwater light, which is 120V with a
300W bulb, can be the only load on that circuit?
If that's the case, the GFCI protection can only be supplied by a
GFCI breaker at the panel. Correct? My helper feels that the
length of the wiring run from the panel to the light is too long
and will cause the GFCI breaker to trip often. He is suggested a
GFCI outlet by the pump pad to feed power to the light and
provide the GFCI protection.
The wiring from the panel to the pump pad is about 60 ft. From
the pad to the light is another 70 feet.
:Warren,
Are you saying that the underwater light, which is 120V with a
300W bulb, can be the only load on that circuit?
REPLY;
YES ! The intent is to limit stray voltage to the pool's water.
SEE THE COPY OF THE CODE SECTION BELOW THAT APPLIES;
680-25. Methods of Grounding
(b) Pool Lighting Fixtures and Related Equipment.
4. The junction box, transformer enclosure, or other enclosure in
the supply circuit to a wet-niche or no-niche lighting fixture
and the field-wiring chamber of a dry-niche lighting fixture
shall be grounded to the equipment grounding terminal of the
panelboard. THIS TERMINAL SHALL BE DIRECTLY CONNECTED TO THE
PANELBOARD ENCLOSURE. THE EQUIPMENT GROUNDING CONDUCTOR SHALL BE
INSTALLED WITHOUT JOINT OR SPLICE EXCEPT AS PERMITTED IN (a) and
(b).
YOU SAID;
If that's the case, the GFCI protection can only be supplied by a
GFCI breaker at the panel. Correct?
REPLY;
NO. Check below showing an exception for a switch, GFI control,
etc. allowed to be installed between that panel and that
underwater light;
680-25. Methods of Grounding
4. The junction box, transformer enclosure, or other enclosure in
the supply circuit to a wet-niche or no-niche lighting fixture
b. Where the underwater lighting fixture is supplied from a
transformer, ground-fault circuit interrupter, clock-operated
switch, or a manual snap switch that is located between the
panelboard and a junction box connected to the conduit that
extends directly to the underwater lighting fixture, the
equipment grounding conductor shall be permitted to terminate on
grounding terminals on the transformer, ground-fault circuit
interrupter, clock-operated switch enclosure, or an outlet box
used to enclose a snap switch.
YOU SAID;
My helper feels that the
length of the wiring run from the panel to the light is too long
and will cause the GFCI breaker to trip often. He is suggested a
GFCI outlet by the pump pad to feed power to the light and
provide the GFCI protection.
The wiring from the panel to the pump pad is about 60 ft. From
the pad to the light is another 70 feet.
REPLY;
YES AND NO. You may install a panel in a pool shed that is fed
from that main dwelling with four insulated conductors including
an insulated grounding conductor ran with that feeder. That pool
shed panel would then be considered the "directly to the
panelboard" that they speak of.
You also must remember that your pool pump and your underwater
light fixture branch circuits must be separate from each other.
You must also remember that the equipment grounding conductor
coming from that panel serving that underwater pool light must be
12 awg or larger and must be contained with that pool light's
branch circuit conductors in a conduit the full length between
that pool light and the panel serving it. No other conductors are
allowed to share that conduit unless they too are GFI protected
at its source of that conduit. The pool pump also requires its
own 12 awg equipment grounding conductor and its branch circuit
must also be contained with that equipment grounding conductor in
its own conduit. Again remember the exception allowing both
dedictated circuits to be in that same conduit as long as they
are both their own GFI protection in that shared conduit.
As for the distance you speak of you may oversize your branch
circuit conductors to offset any voltage drop concerns or you may
install a pool shed panelboard as discribed above.
Also be aware that any metal parts of that pool that is 4" square
or larger must be a part of a 8 awg bonding grid that has nothing
to do with the equipment grouding system of the electrical system.
See the section wiring an in ground pool for inground pools or
above ground pool for above ground pools for more details
included in this home page site called "home wiring".
Hope this helps
Wg
This is 1 item from the Home Wiring
Forum Archives, to go to the main page of the forum archives then click HERE. To go to the main page of the Home
Wiring Site , click HERE.
re: Pool Wiring / GFCI
wirenuts
7:43 am monday september 10, 2001
re: Pool Wiring / GFCI
Jeff Weik
7:52 am monday september 10, 2001
re: Pool Wiring / GFCI
Warren Goodrich
9:00 am monday september 10, 2001
re: Pool Wiring / GFCI
Jeff Weik
12:16 pm monday september 10, 2001
re: Pool Wiring / GFCI
Warren Goodrich
7:14 pm monday september 10, 2001